Capacitive sensor
Capanivo® - CN 4020
Medium Solids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +180°C (-40°F … +356°F) -
Capacitive sensor
Capanivo® - CN 4030
Medium Solids Process pressure -1 bar … +16 bar (-14.5 psi … +232 psi) Process temperature -40°C … +110°C (-40°F … +230°F) -
Capacitive sensor
Capanivo® - CN 4050
Medium Solids Process pressure -1 bar … +6 bar (-14.5 psi … +87 psi) Process temperature -30°C … +80°C (-22°F … +176°F) -
Capacitive sensor
Capanivo® - CN 7100
Medium Liquids Process pressure -1 bar … +10 bar (-14.5 psi … +145 psi) Process temperature -30°C … +100°C (-22 … +212°F) -
Capacitive sensor
Capanivo® - CN 7120 - Stainless steel
Medium Liquids, Solids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +125°C (-40°F … +257°F), CIP/SIP up to 150°C (302°F) -
Capacitive sensor
Capanivo® - CN 7121 - Synthetic
Medium Liquids, Solids Process pressure -1 bar … +10 bar (-14.5 psi … +145 psi) Process temperature -40°C … +125°C (-40°F … +257°F), CIP/SIP up to 150°C (302°F) -
Capacitive sensor
Capanivo® - CN 7130
Medium Liquids, Solids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +125°C (-40°F … +257°F), CIP/SIP up to 150°C (302°F) -
Capacitive sensor
Capanivo® - CN 7150
Medium Liquids, Solids Process pressure -1 bar … +10 bar (-14.5 psi … +145 psi) Process temperature -40°C … +125°C (-40°F … +257°F), CIP/SIP up to 150°C (302°F) -
Capacitive sensor
Capanivo® - CN 8100
Medium Liquids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +125°C (-40°F … +257°F) -
Vibration level switch
Mononivo® - MN 4020
Medium Solids Process pressure -1 bar … +16 bar (-14.5 psi … +232 psi) Process temperature -40°C … +150°C (-40°F … +302°F) -
Vibration level switch
Mononivo® - MN 4030
Medium Solids Process pressure -1 bar … +16 bar (-14.5 psi … +232 psi) Process temperature -40°C … +150°C (-40°F … +302°F) -
Vibration level switch
Mononivo® - MN 4040
Medium Solids Process pressure -1 bar … +16 bar (-14.5 psi … +232 psi) Process temperature -40°C … +150°C (-40°F … +302°F) -
Capacitive sensor
RFnivo® - RF 3100
Medium Solids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +240°C (-40°F … +464°F) -
Capacitive sensor
RFnivo® - RF 3200
Medium Solids Process pressure -1 bar … +25 bar (-14.5 psi … +363 psi) Process temperature -40°C … +240°C (-40°F … +464°F) -
Capacitive sensor
RFnivo® - RF 3300
Medium Solids Process pressure -1 bar … +10 bar (-14.5 psi … +145 psi) Process temperature -40°C … +500°C (-40°F … +932°F) -
Capacitive sensor
RFnivo® - RF 8100
Medium Liquids Process pressure -1 bar … +35 bar (-14.5 psi … +511 psi) Process temperature -40°C ... +200°C (-40°F … +392°F) -
Capacitive sensor
RFnivo® - RF 8200
Medium Liquids Process pressure -1 bar … +35 bar (-14.5 psi … +511 psi) Process temperature -40°C … +400°C (-40°F … +752°F) -
Rotary paddle level switch
Rotonivo® - RN 3001
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +1100°C (-40°F … +2012°F) -
Rotary paddle level switch
Rotonivo® - RN 3002 - Rope
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +600°C (-40°F … +1112°F) -
Rotary paddle level switch
Rotonivo® - RN 3002 - Tube
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +1100°C (-40°F … +2012°F) -
Rotary paddle level switch
Rotonivo® - RN 3002 strengthened rope version
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +600°C (-40°F … +1112°F) -
Rotary paddle level switch
Rotonivo® - RN 3003
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +250°C (-40°F … +482°F) -
Rotary paddle level switch
Rotonivo® - RN 3004
Medium Solids Process pressure -0,9 bar ... +10 bar (-13.1 psi … +145 psi) Process temperature -40°C ... +600°C (-40°F … +1112°F) -
Rotary paddle level switch
Rotonivo® - RN 3005
Medium Solids Process pressure -0,9 bar ... +0,8 bar (-13.1 psi … +11.6 psi) Process temperature -40°C ... +80°C (-40°F … +176°F)
Point Level Measurement
Level detectors detect media at a predefined position depending on the installation position.
Level detectors are mainly installed as full or empty detectors in the upper or lower part of a silo or container. This prevents the silo from overfilling or running empty. In combination with a level sensor, this results in a redundant system which additionally increases plant safety. If a certain fill level is of particular interest, the sensors can also be used as demand detectors.
There are different technologies for level detection, which have their advantages and disadvantages depending on the application. For the selection, numerous process conditions have to be considered, which the sensor technology has to cope with. In addition, the requirements for bulk solids sensors differ from those for liquid sensors. For this reason, UWT offers a broad portfolio of different technologies such as
, and . This allows us to individually address their requirements in order to always provide them with the best possible solution.Typical challenges:
- Media type (e.g. bulk, powder, liquid, paste, etc.)
- Media properties (e.g. bulk density, conductivity, viscosity, etc.)
- Input conditions (e.g. tank material, tank geometry, installation position, installations within the tank, etc.)
- Process conditions (e.g. pressure, temperature, ambient conditions, explosion protection, hygiene requirements, etc.)
In addition to our point level detection sensors our product portfolio also includes a variety of
which unlike limit level sensors can detect the exact level of a medium in real time.FAQs
How does point level measurement work at high temperatures?
Rotary paddle detectors can be used as point level detectors up to a process temperature of 1100 °C. Special materials and bearings must be used. The correct installation position must also be observed.
Which point level switch is suitable for interface measurement (solids in water)??
A tuning fork probe with electronics specially developed for interface measurement is used. The adjustable sensitivity allows the probe to be set to the desired switching point.
Which point level detector is suitable for pressurised hoppers?
A tuning fork is very suitable for bulk materials, e.g. cement and quartz. A process pressure of up to 16 bar is possible with many devices. A rotating paddle detector is also possible up to a process pressure of 10 bar.
Which limit switches are adjustable in the boom length?
Rotary paddle switches, tuning forks, vibrating rods and capacitive limit switches can be adjusted when using a height adjustment sleeve.